Loading Guide

Preparing HPzenAi content

Skip to main content

Energy Meters

RS485 Wiring

Connecting HPzenAi energy meters to the HPzenAi gateway over an RS485 Modbus RTU bus.

RS485 Terminal Identification

Locate the RS485 terminal block on the energy meter — it is marked A and B (sometimes A+/B− or D+/D−). Terminal A is the positive differential line; terminal B is the negative. Swapping A and B is the most common wiring error and prevents communication entirely.

Single Meter Wiring

Steps

  • Run shielded twisted-pair cable from the energy meter RS485 terminals to the HPzenAi Gateway.
  • Connect: Gateway RS485 A → Meter RS485 A.
  • Connect: Gateway RS485 B → Meter RS485 B.
  • Connect the cable shield to earth at the gateway end only — do not earth the meter end.
  • Use twisted-pair cable for all runs, even short ones — single-core cable picks up noise from nearby power wiring.

Multiple Meters on One Bus

Steps

  • Daisy-chain all meter A terminals together and all B terminals together — run the bus from the gateway to each meter in sequence.
  • Do not use a star topology — all devices must be on a single linear bus.
  • Each meter must have a unique Modbus RS485 address (1–32) — configure via the meter DIP switches or configuration menu.
  • Fit a 120 Ω termination resistor between A and B at the furthest meter on the bus.
  • Maximum cable run: 1200 m at 9600 baud; reduce to 800 m or lower baud rate in high-interference environments.

Cable Specification

Steps

  • Use 2-core shielded twisted-pair (STP) RS485 cable — Belden 9842 or equivalent.
  • Minimum conductor size: 0.2 mm² (24 AWG) for runs up to 300 m; use 0.5 mm² (20 AWG) for longer runs.
  • Cable impedance: 120 Ω (matched to the RS485 standard).
  • Route RS485 cables in a separate duct from 230V / 415V power cables — maintain at least 100 mm separation.
  • Avoid routing near VFDs, inverters, and motor starters — these are major sources of RS485 interference.

Powering the Energy Meter

RS485 carries communication only — it does not supply power. Each energy meter requires a dedicated 12V DC supply connected to its power input terminals. Use an HPzenAi PWR-1P-12V-15W or PWR-3P-12V-12W adapter mounted in the same panel. Ensure the 12V supply is rated for the total load of all connected devices.

Modbus Address Configuration

Steps

  • Factory default Modbus address is 1 — suitable for a single meter on the bus.
  • For multiple meters, assign a unique address to each before connecting to the shared bus.
  • Address configuration is done via the meter front panel buttons or DIP switches — refer to the meter label for the procedure.
  • In the HPzenAi app, the RS485 Scan automatically detects addresses — no manual address entry is needed in the app.