Motor Controllers

Installation & Setup Guide

How to mount and wire the MX-1P control module into an existing single-phase motor starter panel.

Section: Moto-X 1-Phase

Safety Requirements

The MX-1P module wires to the control coil circuit of an existing starter — however the panel still contains live 220V AC mains wiring. All work inside the starter enclosure must be performed with the mains supply fully isolated and locked off.

Steps

  • Switch off and lock out the mains circuit breaker feeding the motor starter before opening the enclosure.
  • Confirm 0V AC between Line and Neutral at the starter input terminals using a multimeter before touching any wiring.
  • The MX-1P control circuit (12V DC and RS485) can be connected by a competent technician. The coil output wiring must be handled by a qualified electrician where it passes near 220V mains terminals.
  • Never connect the MX-1P V+ or RS485 terminals to mains voltage — the module operates on 12V DC only.
  • Ensure all 220V mains connections remain intact from the previous installation — only the coil control wiring (A1/A2) is modified when installing the MX-1P.

Tools Required

Visual reference coming soon
Visual reference for the tools needed before starting this guide.

Tool Checklist

PreviewQuantityItemDetails
× 1Flat-Head Screwdriver (3 mm)For MX-1P terminal block screws (control circuit, RS485, 12V DC)
× 1Flat-Head Screwdriver (5 mm)For mains terminal blocks inside the existing starter (if adjustments needed)
× 1Wire StrippersTo prepare 1.0 mm² and 1.5 mm² control cable ends
× 1MultimeterTo verify 0V AC at mains terminals before work and 12V DC at module after power-up
As requiredRS485 Shielded Twisted-Pair Cable1.0 mm² shielded cable for RS485 A and B connection from module to gateway
As required1.5 mm² Control CableFor wiring from MX-1P switching output to contactor coil A1 terminal
× 1DIN Rail Snips or HacksawIf extending the DIN rail inside the existing enclosure to mount the MX-1P module
Item 1× 1

Flat-Head Screwdriver (3 mm)

For MX-1P terminal block screws (control circuit, RS485, 12V DC)

Item 2× 1

Flat-Head Screwdriver (5 mm)

For mains terminal blocks inside the existing starter (if adjustments needed)

Item 3× 1

Wire Strippers

To prepare 1.0 mm² and 1.5 mm² control cable ends

Item 4× 1

Multimeter

To verify 0V AC at mains terminals before work and 12V DC at module after power-up

Item 5As required

RS485 Shielded Twisted-Pair Cable

1.0 mm² shielded cable for RS485 A and B connection from module to gateway

Item 6As required

1.5 mm² Control Cable

For wiring from MX-1P switching output to contactor coil A1 terminal

Item 7× 1

DIN Rail Snips or Hacksaw

If extending the DIN rail inside the existing enclosure to mount the MX-1P module

What's in the Box

Visual reference coming soon
Visual reference for the items included in the package.

Included Items

PreviewQuantityItemDetails
× 1MX-1P Control ModuleMain IoT control module for DIN rail mounting
× 1RS485 Terminal Block2-position screw terminal for RS485 A and B wiring
× 112V DC Input Terminal2-position screw terminal for control power supply connection
× 1DIN Rail ClipSpring clip for 35 mm DIN rail mounting
× 1Quick Installation CardPrinted reference card with terminal diagram and commissioning steps
Item 1× 1

MX-1P Control Module

Main IoT control module for DIN rail mounting

Item 2× 1

RS485 Terminal Block

2-position screw terminal for RS485 A and B wiring

Item 3× 1

12V DC Input Terminal

2-position screw terminal for control power supply connection

Item 4× 1

DIN Rail Clip

Spring clip for 35 mm DIN rail mounting

Item 5× 1

Quick Installation Card

Printed reference card with terminal diagram and commissioning steps

Removing an Old Smart Controller

The MX-1P is intended for retrofit use. Keep the existing single-phase starter, overload relay, and motor power wiring in place, and remove only the previous smart or manual control method before installing the MX-1P control circuit.

Steps

  • Do not remove the existing starter contactor or overload relay if they are in serviceable condition.
  • Disconnect old timer, float-switch, or manual switch wiring only from the coil control side where the MX-1P output will take over.
  • Retain any healthy overload trip contact in series with the contactor coil so hardware overload protection continues to operate independently of the smart controller.
  • If the existing starter enclosure is damaged, corroded, or has loose terminals, replace the enclosure or the complete starter assembly before installing the MX-1P.
  • If the existing panel already contains another automation controller, remove or isolate its coil output so it cannot issue conflicting start and stop commands alongside the MX-1P.

Guided Help Center

Step 1 / 4
9:41
1

Identify any old controller, timer, or automation relay connected to the contactor coil circuit.

Step 1 / 4

Panel Mounting

Mount the MX-1P module on the existing DIN rail inside the starter enclosure, or on a supplementary DIN rail section added beside the existing components.

Visual reference coming soon

Steps

  • With the mains supply isolated, open the existing starter enclosure.
  • Identify a free section of DIN rail (minimum 40 mm) adjacent to the existing contactor. If no free space exists, add a short DIN rail section using adhesive DIN rail or a bolt-on extension.
  • Clip the MX-1P module onto the DIN rail — press down on the spring clip until it snaps into place.
  • Route 12V DC and RS485 wiring paths away from 220V mains cable routes — maintain at least 30 mm separation or use a cable duct divider.
  • Fit the 12V DC DIN rail power supply if not already present — clip it onto the DIN rail next to the MX-1P module.

Guided Help Center

Step 1 / 4
9:41
1

Open the enclosure and identify a free DIN rail section near the existing starter components.

Step 1 / 4

Control Circuit Wiring

The MX-1P switching output connects to the existing contactor coil circuit. Only the A1 and A2 coil connections change — all mains (L, N, motor, capacitor) wiring remains untouched.

Visual reference coming soon

Steps

  • Identify the contactor coil terminals A1 and A2 inside the existing starter. These are the small terminals (typically 2.5 mm² screws) connected to the on/off switch, timer, or push-button circuit.
  • Disconnect the existing control wiring from A1 (the switched side). Leave A2 connected — it typically goes to Neutral.
  • Connect a 1.5 mm² wire from the MX-1P SWITCHING OUTPUT terminal to contactor coil A1.
  • If the existing starter has an overload relay trip contact wired in the coil circuit, keep it in series between the MX-1P output and A1 — this preserves hardware overload protection.
  • Connect the 12V DC power supply positive (+) output to MX-1P V+, and negative (−) to MX-1P V−.
  • Connect RS485 cable: A core → MX-1P RS485-A terminal, B core → MX-1P RS485-B terminal. Connect cable shield to panel earth at panel end only.
  • Verify the coil voltage selector on the MX-1P matches your contactor coil voltage (230V AC or 24V DC) before restoring power.

Guided Help Center

Step 1 / 4
9:41
1

Locate the contactor coil terminals A1 and A2 inside the existing starter panel.

Step 1 / 4

Commissioning & First Start

Steps

  • Close and latch the enclosure. Restore 12V DC power first — confirm MX-1P LED turns green (running) or flashes blue (pairing mode if not yet linked).
  • Restore mains supply to the starter panel.
  • Complete Gateway Linking before issuing the first start command — see the Gateway Linking guide.
  • Once linked, open the HPzenAi app and tap the motor controller tile. Tap Manual Control → Start.
  • Confirm the contactor energises (audible click) and the motor starts. Verify the pump delivers water or the equipment runs as expected.
  • If the motor hums but does not start, check the capacitor wiring — a missing or failed capacitor is the most common cause on single-phase motors.
  • Set overload relay current dial on the contactor to the motor nameplate FLA (if not already set).