How to connect the SP-3P's built-in MX-3P module to an HPzenAi gateway over RS485 and link it in the app, whether the gateway is panel-integrated or external.

Section: Starter 3-Phase

What You'll Need

Steps

  • SP-3P assembly installed, 12V DC control power on, and three-phase mains supply restored.
  • HPzenAi gateway (GW-W1 Wi-Fi or GW-XR1 SIM/RF) available, whether integrated within the panel arrangement or installed externally, and connected to the HPzenAi platform.
  • RS485 shielded twisted-pair cable pre-run from the SP-3P panel to the gateway.
  • HPzenAi app installed and logged in to your project account.
  • MX-3P Modbus address — factory default is Address 1.

RS485 Wiring to Gateway

The SP-3P exposes MX-3P RS485-A and RS485-B terminals on the side of the assembly. Multiple SP-3P units can share the same RS485 bus to the gateway. The RS485 link is required whether the gateway is integrated into the panel arrangement or installed externally.

Visual reference coming soon

Steps

  • Route RS485 shielded cable from the SP-3P assembly to the gateway in the low-voltage cable duct — separate from the 415V mains cables.
  • At SP-3P end: A core → RS485-A; B core → RS485-B. Shield drain → panel earth bar.
  • At gateway end: A core → RS485-A; B core → RS485-B. Shield floating.
  • If SP-3P is the last device on the bus and the run exceeds 10 m: fit 120 Ω termination resistor between RS485-A and RS485-B at the SP-3P terminals.
  • Assign unique Modbus addresses if multiple SP-3P or MX-3P modules are on the same bus.

RS485 Scan & Device Detection

Steps

  • Open the HPzenAi app, tap the gateway tile, and open gateway settings.
  • Tap RS485 → Scan Devices.
  • The SP-3P built-in module appears as 'Motor Controller — SP-3P' with its Modbus address and current phase status.
  • If not detected: confirm the MX-3P LED is lit on the SP-3P assembly (12V DC present), check RS485 polarity, and verify no duplicate Modbus addresses on the bus.
  • If phase sense wires are connected, the scan result also shows the current phase status (R, S, T present/absent).

Add Starter to Your Project

Step 1 / 7
9:41
1

In scan results, tap the detected SP-3P device

Step 1 / 7

Verifying the Connection

Steps

  • Confirm the starter tile shows Online (green) in the app.
  • Tap Manual Control → Start. The SP-3P contactor should click and the motor should run.
  • Check that the app shows all three phases as present in the device status panel.
  • Tap Stop and confirm the motor stops and the contactor releases.
  • Runtime hours and phase status data appear in Device → Status after the first successful start.