Loading Guide

Preparing HPzenAi content

Skip to main content

Relay Controllers

RS485 Wiring

Connecting relay controllers to the HPzenAi gateway over an RS485 bus.

RS485 Wiring Video Guide​

HPzenAi Relay Controller — RS485 Bus Wiring to Gateway
Walkthrough video coming soon

Tools Required​

RS485 wiring uses low-voltage signal cable. No specialist tools are required beyond standard wiring tools.

Visual reference coming soon
Visual reference for the tools needed before starting this guide.

Tool Checklist​

PreviewQuantityItemDetails
× 1Flat-Head Screwdriver (3 mm)For tightening RS485 terminal block screws on the controller and gateway
× 1Wire StrippersTo prepare twisted-pair cable ends before insertion into terminals
As requiredRS485 Shielded Twisted-Pair Cable1.0–1.5 mm² 2-core shielded cable — not included, sourced separately
× 1120 Ω Termination ResistorFor bus termination at the last device on runs longer than 10 m
As requiredCable Labels / MarkersTo label A and B terminals at each end of the cable run
Item 1× 1

Flat-Head Screwdriver (3 mm)

For tightening RS485 terminal block screws on the controller and gateway

Item 2× 1

Wire Strippers

To prepare twisted-pair cable ends before insertion into terminals

Item 3As required

RS485 Shielded Twisted-Pair Cable

1.0–1.5 mm² 2-core shielded cable — not included, sourced separately

Item 4× 1

120 Ω Termination Resistor

For bus termination at the last device on runs longer than 10 m

Item 5As required

Cable Labels / Markers

To label A and B terminals at each end of the cable run

RS485 Terminal Identification​

The relay controller has a 2-position RS485 terminal block labelled A and B on the controller PCB or enclosure label. RS485 A is the positive differential line (+); RS485 B is the negative differential line (−). The HPzenAi gateway has an equivalent A and B terminal block on its RS485 port.

Visual reference coming soon

Steps​

  • RS485 A (+) — positive differential signal line; connect to gateway RS485 A.
  • RS485 B (−) — negative differential signal line; connect to gateway RS485 B.
  • Swapped A/B is the single most common installation error — verify polarity before powering on.
  • The RS485 bus carries communication signals only — it does not carry power. Each device requires a separate 12V DC supply.

Wiring a Single Relay Controller to the Gateway​

For a single relay controller, wire directly from the gateway RS485 port to the controller RS485 terminal block using a twisted-pair cable.

Visual reference coming soon

Steps​

  • Run a twisted-pair shielded cable from the gateway RS485 terminal to the relay controller RS485 terminal.
  • Connect the yellow wire (or A-labelled core) to RS485 A on both the gateway and the controller.
  • Connect the green wire (or B-labelled core) to RS485 B on both the gateway and the controller.
  • If the cable has a shield drain wire, connect it to the ground terminal at the gateway end only — do not connect the shield at the device end.
  • Tighten all terminal screws firmly.
  • For a single device on a short cable run (under 10 m), a termination resistor is optional but recommended.

Wiring Multiple Controllers on One RS485 Bus​

Multiple relay controllers (and other RS485 devices) can share a single RS485 bus connected to the gateway. Wire them in a daisy-chain topology — avoid star or branch wiring configurations.

Visual reference coming soon

Steps​

  • Connect the gateway RS485 A and B terminals to the first device on the bus.
  • From the first device's RS485 A terminal, run a cable to the RS485 A terminal of the second device.
  • Repeat for RS485 B — all A terminals daisy-chained together, all B terminals daisy-chained together.
  • Continue the daisy-chain to each additional device in sequence.
  • Do not create star or branch connections — all devices must be in a single chain from gateway to last device.
  • Assign each device a unique RS485 address (1–32) — devices sharing an address will conflict and neither will be detected.
  • Fit a 120 Ω termination resistor between the A and B terminals of the last device on the bus.
  • Maximum cable run: 1,200 m at 9600 baud with appropriate cable.

Setting the RS485 Device Address​

Each relay controller on the RS485 bus must have a unique Modbus address. The address is set via the physical DIP switches or jumpers on the controller PCB, or via the app during commissioning.

Steps​

  • The factory default RS485 address is 1.
  • For the first controller, leave the address at 1 if it is the only device on the bus.
  • For additional controllers, set each to a unique address — 1, 2, 3, etc.
  • To change the address via DIP switches: power off the controller, set the DIP switch combination for the desired address (refer to the address table printed inside the enclosure lid), then power on.
  • To change the address via the app: go to Device Settings → RS485 → Device Address — this requires the controller to already be detected at its current address.
  • After changing the address, perform an RS485 scan from the gateway to re-detect the device at its new address.

RS485 Scan and Device Discovery​

After wiring, perform an RS485 scan from the HPzenAi app to detect the relay controller on the bus.

Steps​

  • Ensure the relay controller is powered on and the RS485 cable is connected to the gateway.
  • Open the HPzenAi app → Main Menu → Gateway → select your gateway.
  • Tap RS485 Scan.
  • Wait 30–60 seconds for the scan to complete.
  • The relay controller will appear in the detected devices list.
  • Tap Link to add the controller to your gateway and account.
  • If the controller does not appear, verify A/B polarity, confirm the controller has 12V power, and check for duplicate addresses.

Guided Help Center

Step 1 / 8
9:41
1

Open the HPzenAi app.

Step 1 / 8

RS485 Wiring Checklist​

Steps​

  • RS485 A connected to A and RS485 B connected to B at all devices — not swapped.
  • Daisy-chain topology used — no star or branch connections.
  • Each relay controller has a unique address (no duplicates).
  • 120 Ω termination resistor fitted between A and B at the last device on the bus.
  • Cable shield connected to ground at the gateway end only.
  • RS485 cable routed separately from 230V mains power cables.
  • All terminal screws firmly tightened.
  • RS485 scan completed from the app — all controllers detected and linked.

Important RS485 Wiring Notes​

Steps​

  • RS485 cables must not share conduit or trunking with 230V AC mains cables — route them separately to avoid electromagnetic interference.
  • Maximum RS485 bus length is 1,200 m at 9600 baud — longer runs require a lower baud rate or RS485 repeater.
  • Use shielded twisted-pair cable for all RS485 runs — unshielded cable is susceptible to interference, especially near inverters or variable-frequency drives.
  • A missing or incorrectly placed termination resistor is a common cause of bus instability when multiple devices are connected.